Medium voltage switchboards

From primary switchgear to the ring main unit.

Four ranges across medium voltage distribution: PIX Easy primary switchgear, package substations, gas-insulated ring main units and capacitor banks.

17.5 kV
PIX Easy, rated voltage
36 kV
Package substations, up to
630 A
Ring main units, rated current
9 MVAR
Capacitor banks, up to
The ranges

Four ranges, and what each one is for.

Rated values for every range are tabulated below.

A row of PIX Easy switchgear cubicles lined up across the assembly bay, each with a protection relay, metering and a withdrawable circuit-breaker compartment
PIX Easy · 12 / 17.5 kV

Primary air-insulated switchgear

The board between the incoming network and everything downstream.

  • Manufactured under the Schneider Electric PIX Easy licence — the licence is signed; the licence certificate is in process
  • Designed to the applicable IEC standards
  • EasyPact EXE vacuum circuit breaker
  • Rated current up to 2,500 A
  • Internal arc classification AFLR 31.5 kA for 1 s
  • Can be equipped with smart infrastructure for remote monitoring and control
Package substation enclosures standing outside the hall
Package substations · up to 36 kV

Transformer, MV and LV in one enclosure

Factory-assembled, so site work is limited to cable connection.

  • Transformer power from 50 kVA to 3 MVA
  • MV compartment with air-insulated or SF6 ring main unit
  • LV and MV compartments with double doors
  • Natural or forced cooling
  • IP 54 outdoor-rated enclosure; RAL 7033 or 7035, stone paint, or a color to customer request
  • Smart infrastructure for remote monitoring and control of the transformer and the LV and MV equipment
  • Applications: transmission and distribution networks, and solar power plants
A worker handling medium voltage insulators and contacts
GIS RMU · 17.5 kV

Gas-insulated ring main units

Sealed-for-life secondary distribution switchgear.

  • Fully SF6 gas-insulated, sealed-for-life
  • Rated current 630 A
  • Rated short-time withstand current 21 kA
  • Rated peak withstand current 52.5 kA
  • Four-element construction: switching compartment, drive mechanism, fuse compartment and cable connection compartment
  • Applications: transmission and distribution networks, and solar power plants
A finished switchroom with panels installed
Capacitor banks · up to 9 MVAR

Power factor correction

Compensation built in steps, so it follows the load instead of sitting fixed against it.

  • Banks up to 36 kV and up to 9 MVAR
  • Metal-clad cubicles, open-rack, or inside a package substation
  • Fixed or automatic switching steps
  • Forced cooling at IP 54
  • Smart-ready over Modbus TCP, RS485 and IEC 61850
  • Main switching device: load-break switch or circuit-breaker; step switching by contactor or circuit-breaker
  • Cable entry from the bottom, with high protection for the busbar and the capacitor banks
  • Applications: voltage-drop improvement in transmission, reactive power compensation for motor systems, and harmonic filtering
How medium voltage is built

Licence-built cells, configured to your single-line diagram.

Metal-clad, arc-classified cells to the IEC 62271 series, built under licence and configured to your single-line diagram.

Compliance evidence is issued against a named enquiry.

Rows of finished cubicles seen from above in the group's manufacturing hall
MV Assembly
Operating
TEPCO Group manufacturing.
Two PIX Easy cubicles on their pallets, each with a protection relay and metering in the upper compartment and a withdrawable circuit-breaker door below
PIX Easy air-insulated switchgear. Configuration per single-line diagram.
PIX Easy · technical data

Rated values.

Parameter12 kV · 17.5 kV
Rated voltage12 kV · 17.5 kV
Rated power-frequency withstand voltage28 kV rms · 38 kV rms
Rated lightning impulse withstand voltage75 kV peak · 95 kV peak
Rated frequency50 / 60 Hz
Rated continuous currentUp to 2,500 A
Rated short-time withstand current, 3 s25 – 31.5 kA
Rated peak withstand current65 – 81.9 kA peak
Degree of protectionIP 4X
Electrical characteristics according to IEC standards. Values are given for 12 kV first, 17.5 kV second.
A TEPCO package substation enclosure with ventilation louvres and access doors, on a steel base frame
Package substation enclosure. Transformer, MV and LV compartments inside one shell.
Package substations · technical data

Rated values.

ParameterValue
Rated voltageUp to 36 kV
Transformer apparent powerUp to 3 MVA
Rated frequency50 / 60 Hz
Power-frequency test voltageUp to 70 kV rms
Impulse withstand voltage170 kV peak
Rated secondary voltage230 / 400 / 690 V
MV switch rated current630 A
Standard colorRAL 7033
Degree of protectionIP 54
Designed to IEC 62271-100, -102, -103, -105 and -200, and DIN VDE 0670 and 0671.
Three-cubicle gas-insulated ring main unit with mimic fascia, operating ports and a low voltage compartment above
Three-cubicle ring main unit. Arrangement per single-line diagram.
GIS ring main units · technical data

Rated values.

ParameterValue
Rated voltage17.5 kV
Rated power-frequency withstand voltage, 1 min38 kV rms
Rated lightning impulse withstand voltage95 kV peak
Rated frequency50 / 60 Hz
Rated current630 A
Rated short-time withstand current21 kA rms
Rated peak short-circuit current52.5 kA peak
Designed to IEC 60265, IEC 62271-1, IEC 62271-100, IEC 62271-200 and IEC 62271-105.
Two medium voltage capacitor units with insulator bushings, shown side by side
Medium voltage capacitor units. Bank rating and step count per the power factor study.
MV capacitor banks · technical data

Two standard banks.

Parameter5.4 MVAR bank · 9.0 MVAR bank
Power transformer size20 – 25 MVA · 40 MVA
Capacitor bank power5.4 MVAR · 9.0 MVAR *
Step configuration1.8 + 1.8 + 3.6 MVAR · 1.8 + 3.6 + 3.6 MVAR
Mass, outdoor6 tonnes · 8 tonnes
Dimensions, outdoor4250 × 3750 × 2400 mm
Dimensions, indoorModular, by number of steps
Rated voltage12 / 17.5 / 24 / 36 kV
Rated frequency50 / 60 Hz
* Higher power ratings are available upon request. Values are given for the 5.4 MVAR bank first, the 9.0 MVAR bank second.